From the irc and other plumbing codes.
Plumbing vent height above roof.
Flagpoling of vents shall be prohibited except where the roof is used for assembly purposes or parking.
C the vent pipe is increased to not less than 3 in.
Vents within 10 feet 3048 mm of a part of the roof that is used for assembly purposes or parking shall.
How high should the plumbing vents be above there roof.
6 inches above nearest roof surface nearest accommodates sloped roof i e.
Vent pipes should extend to outdoors above the building roof and should terminate vertically not less than 6 above the roof surface nor more than 24 and must be at least 12 from any vertical surface such as a nearby sidewall.
12 inches from nearest vertical surface.
Such as the side wall of an upper story on the building.
Open vent pipes that extend through a roof shall be terminated not less than 6 inches 152 mm above the roof.
The slope is about 4 high for every 12 horizontal.
4 except for a fresh air inlet where a vent pipe is terminated in open air the terminal shall be located.
Used most commonly at an island sink or vanity the vents are also located in the attic to prevent the roof penetrations as seen above on the front roof line elevation.
Think about it when have you ever seen a plumbing vent on the front roof line.
Open vent pipes that extend through a roof shall be terminated at least 6 inches 152 mm above the roof or 6 inches 152 mm above the anticipated snow accumulation whichever is greater except that where a roof is to be used for any purpose other than weather protection the vent extension shall be run at least 7 feet 2134.
P3103 1 roof extension.
Plumbing vent height above sloped roof.
Where a roof is to be used for assembly or as a promenade observation deck sunbathing deck or similar purposes open vent pipes shall terminate not less than 7 feet 2134 mm above the roof.
The true vent is aligned vertically and attaches to your drain line through the roof.
I have a main vent and a sink vent and both are only 6 high above the roof.
Vent pipes shall be extended separately or combined of full required size not less than 6 inches 152 mm above the roof or fire wall.
Nearest vertical surface distance to plumbing vent.
Above the roof plumbing vent height.
This is best implemented if a fixture rests close to the stack and the top floor of your home allowing the stack to serve as a vent.
Roof surface distance to plumbing vent.
Understanding the plumbing vent.